Add the insulated conductor areas
For an ordinary US raceway run longer than 24 inches, start with the complete cross-sectional area for each conductor, including its insulation. Suppose your published conductor dimensions are 0.0133 square inches for six conductors and 0.0211 square inches for two others. The first group occupies 0.0798 square inches and the second occupies 0.0422. Together, eight conductors occupy 0.1220 square inches. Enter the two rows as 0.0133, 6 and 0.0211, 2. Conduit Fill Calculator
Compare the occupied area with the full internal area
For ¾-inch EMT, the tool uses a full internal area of 0.533 square inches. Divide 0.1220 by 0.533 and multiply by 100 to obtain 22.889% fill. The ordinary-run limit used here for three or more conductors is 40%, corresponding to 0.2132 square inches. This leaves 0.0912 square inches up to that area limit. Use the full inside area when entering a custom raceway. A value already reduced to 40% would apply the allowance twice. Siemens wiring guidelines and EMT dimensions
Check what changes when the conductor count changes
If the second group increases to three conductors, their area becomes 0.0633 square inches. The total becomes 0.1431 square inches. That still fits within the 0.2132-square-inch allowance for the ¾-inch example. In ½-inch EMT, which has 0.304 square inches of internal area, those same conductors occupy about 47.07%, above the 40% threshold.
Count individual conductors for this example. A single conductor uses a 53% ordinary-run limit, two use 31%, and three or more use 40%. A multiconductor cable may count as one item under the applicable rules. Confirm the adopted requirements for the actual installation, including special raceway conditions, ampacity and pulling limits. NFPA Chapter 9 table material