Conduit Fill Calculator
Compare insulated conductor areas with the internal area of an ordinary US raceway run.
Mixed conductor groups
Enter each insulated conductor’s published cross-sectional area in square inches and its count. Include equipment grounding conductors in the fill calculation.
Worked example
Eight conductors occupying 0.122 square inches in ¾ inch EMT with 0.533 square inches of internal area fill about 22.89% of the raceway.
Compare an EMT size
Switch between six EMT areas from ½ inch through 2 inches. For other raceways, select manual entry and use a published full internal area.
How to use the Conduit Fill Calculator
- 1
Choose an EMT trade size or enter the full internal area of your raceway in square inches.
- 2
Enter one row for each conductor size and insulation, using the complete insulated area and a whole count.
- 3
Read the occupied area, the ordinary-run limit and the remaining or excess area.
Frequently Asked Questions
Which fill limits are used?
The ordinary-run calculation uses the NEC Chapter 9 Table 1 limits of 53% for one conductor, 31% for two and 40% for three or more. The special nipple allowance is outside this tool’s scope.
Can I use a different raceway or wire insulation?
Enter the published total internal area of the raceway and the cross-sectional area of each insulated conductor. Use the full cable area when your applicable rules count a cable as one. The result checks area only; verify the adopted code, conductor ampacity and installation details separately.
Do I enter a bare copper area for an insulated wire?
Use the entire insulated cross-sectional area. A bare conductor area excludes insulation and would understate the space occupied.